PADUNGSILPA ENGINEERING

PSE-WATERTIGHTTANK SUMP

A watertight PSE-FRP tank sump for underground fuel-tank systems, designed to help prevent water ingress, fuel contamination and equipment damage, with vacuum-test verification.

PSE Watertight Tank Sump
ISO 9001:2015
Quality Control
FRP + LRTM
Manufacturing
VACUUM TEST
Leak Verification
5 YEARS
Specified Warranty
PSE-FRP Watertight Tank Sump
PRODUCT OVERVIEW

PSE-FRP Watertight Tank Sump

The product was developed from PADUNGSILPA ENGINEERING's fuel-tank and service-station experience to address water ingress into tank sumps, which can contaminate fuel systems or damage installed equipment.

The sump is manufactured using the LRTM process with polyester resin and Fiberglass Reinforcement Core Combination Mat, under the ISO 9001:2015 quality-control system stated in the PSE product specification.

KEY FEATURES

Designed for tightness and verifiable installation

01

FRP Watertight Tank Sump

A watertight FRP tank sump designed to help prevent water ingress around equipment above an underground tank, reducing risks of fuel contamination and equipment damage.

02

LRTM Manufacturing

Manufactured using Lite Resin Transfer Molding (LRTM) with fiberglass reinforcement for strength and consistent product quality.

03

Underground-Duty Materials

Uses polyester resin specified for underground environmental resistance together with Fiberglass Reinforcement Core Combination Mat.

04

Installation-Friendly Size

The product specification states an approximately 1.48 × 1.10 m, 16-sided FRP sump with a minimum wall thickness of 6 mm.

05

Vacuum-Test Verification

Leak tightness can be checked by vacuum testing, with the PSE work procedure showing multiple verification points during installation.

06

5-Year Warranty

The product specification states a 5-year quality warranty, subject to the applicable project documents and warranty conditions.

PRODUCT SPECIFICATION

Core technical data

The data below is based on the supplied PSE WATERTIGHT TANK SUMP specification. Project execution should follow approved drawings and project-specific purchase documents.

Type
FRP WATERTIGHT TANK SUMP
Approx. Size
1.48 × 1.10 m
Geometry
16-sided
Wall Thickness
≥ 6 mm
Process
LRTM
Verification
VACUUM TEST
INSTALLATION PROCESS

8 steps from the PSE installation procedure

Remove Existing Tank Sump
STEP 01

Remove Existing Tank Sump

The existing tank sump is removed by the main contractor in accordance with project scope and safety requirements.

Clean Existing Steel Collar
STEP 02

Clean Existing Steel Collar

The existing steel collar surface is prepared and cleaned before base-sump installation.

Install Base Sump
STEP 03

Install Base Sump

The base sump is installed at the prepared location in accordance with the installation details.

First Vacuum Test
STEP 04

First Vacuum Test

The first vacuum test verifies tightness after the base-sump installation stage.

Install Piping and Equipment
STEP 05

Install Piping and Equipment

Piping and equipment are installed within the tank sump by the responsible piping contractor.

Install Corbel Part
STEP 06

Install Corbel Part

The corbel section is installed to complete the tank-sump assembly for the next verification stage.

Second Vacuum Test
STEP 07

Second Vacuum Test

A second vacuum test is performed after major sump components and related systems are assembled.

Final Vacuum Test After Backfill
STEP 08

Final Vacuum Test After Backfill

A third vacuum test is performed after backfilling to verify the completed installation.

ENGINEERING DETAILS

Assembly details and installation drawing

PSE Watertight Tank Sump corbel detail

Corbel Part Detail

Illustration from the PSE installation procedure showing the corbel section used during tank-sump assembly.

PSE Watertight Tank Sump final detail

Completed Assembly Detail

Used to illustrate component locations and assembly details during verification before and after backfilling.

PSE Watertight Tank Sump installation drawing

PSE-WATERTIGHT TANK SUMP Installation Drawing

This drawing is presented for product information. Construction must follow the approved project drawings and applicable project details.

PADUNGSILPA GROUP

Need PSE-WATERTIGHT TANK SUMP information for your project?

Contact our team for product details, installation drawings, piping coordination and project scope for service-station applications.

Contact PADUNGSILPA GROUP